Very often we notice separation or cracks in locations where brick masonry meet concrete – say a column or slab due to differential or uneven expansion (or contraction) of the two dissimilar materials. Also often external crack in plaster are noticed due to shrinkage of external plaster. These are often inevitable unless adequate precautionary measures are taken.

The following procedures should be adopted to repair such cracks:

Ø Open the cracks into ‘V’ groove; clean and moisten the groove.

Ø Apply a priming cum bonding coat of POLYALK EP / cement slurry in the proportion 1:0.5 (by wt.) with brush to grooved surface.


Ø Immediately, fill the groove with polymer modified mortar, which is prepared by mixing

2 kgs. POLYALK EP
5 kgs. Cement
15 kgs. Sand Graded

After 15-20 minutes level the surface with steel trowel.

Ø After 24 hours, cure by sprinkling water for 2-3 days.


Ø Further finishing process can then follow.